91+ 9823804196

svelectronics@live.com

PRODUCTS

Hornbill 1000 & 2000

Hornbill Static switch have different user selectable parameters with DSP control. It is excellent performance enhancement system useful for Data center, Process Automation, Power plant, Healthcare, Telecom, Broadcasting, Industry type of environment

ADD TO WISHLITE

  • 32 bit DSP controlled UPS
  • Automatic instantaneous transfer and retransfer without cross connection of sources
  • Interlocking of hardware & software to avoid make - before switching
  • Enhanced monitoring and diagnostics
  • RS 232 or RS 485 interface with MODBUS protocol
  • Redundant power supply
  • 19" Rack mountable
  • Complies with IEEE 446
  • Natural air cooled for highest reliability

MODEL

Hornbill 1000 Hornbill 2000

Input / Output

Nominal Voltage

110 / 115/230 / 240 VAC (1 Ph + N)

Voltage Tolerances

+/- 15%

Frequency Tolerances

wide band 40 - 70 Hz Auto Selectable

Power Capacity

16A / 32A / 63A

No. of Switching Poles

SINGLE TWO

Overload Capacity

110% for 1 hour, 150% for 60 s, 200% for 10 s, 1000% for 100 ms

Duty

Continuous

Load Power Factor range

0.2 to unity leading or lagging

Source Voltage Distortion

> 10% THD

Controller

32 bit DSP

Controller

32 bit DSP

Switch

Transfer

5 ms in sync & No sync

Voltage regulation

± 2%

Retransfer

< 5 ms in sync & No sync

Manual Bypass

Provided

Efficiency (Ref. IEC 60146-1-1)*

≥ 99% ≥ 98%

Environmental

Operating Temperature

0 to 40°C

Storage Temperature

0 to 70°C

Relative Humidity

Up to 95% (Non Condensing)

Acoustic Noise @1 m (Ref. ISO 3746)

≤ 45 dBA

Altitude

Physical)

Cooling

Natural

Color

RAL 7016

Cable Entry

Back

Dimensions

3 U (485 x 450 x 132 mm)

Installation

19” Rack Mountable

User Interface

Indications

Source 1 Healthy, Source 1 Priority, Source 1 Feeding, Source 1 Manual bypass ON, Output ON

Source 2 Healthy, Source 2 Priority, Source 2 Feeding, Source 2 Manual bypass ON, No Sync

Fault Indication

Fault Indication

Standards

IEC 62310-1, IEEE 446

Other Features

RS 485 MODBUS, Ethernet connectivity (optional)