91+ 9823804196

svelectronics@live.com

PRODUCTS

Lora 3000

The IORA 3000 Active Harmonic Filter is a state of the art harmonic filter, which measures level of current harmonic in the supply line and eliminates it by generating the counter harmonics, in real time. The IORA 3000 is available upto 600 Amps rating which, is the highest in the world.

ADD TO WISHLITE

  • Modular construction, most unique design concep
  • Based on Floating point 32 bit DSP
  • Selective harmonic elimination methods. CT can be connected in load as well as in source
  • Works upto 690 VAC (Optional
  • Ethernet based Remote monitoring and 7 inch SVGA touch screen display
  • Lower audible noise
  • Compact in size
  • Compliant to protection up to IP 51 (Optional)
  • Internal CAN communication
  • Employs high speed IGBTs in power circuit
  • Closed loop active filter with source current sensing
  • High attenuation up to 96% of individual harmonics
  • Programmable selective harmonic elimination
  • PF compensation, leading as well as lagging
  • Load balancing
  • Helps in achieving the compliance with power quality regulations like IEEE 519
  • IEC/EN 62040-2 category C3

MODEL

IORA 3000

Rating (A)

30 60 100 200 300 400 600 30 60

Electrical Specifications

utility Connection Method

3 Phase, 4 Wire

Utility Frequency

50/60 Hz, +/- 5%

Utility Voltage V1

400 V AC +10%, -15%

Filter Current I1 (A)

30 60 100 200 300 400 600 30 60

Utility Voltage V2

480 V AC +10%, -15%

Filter Current I2 (A)

25 50 80 165 250 330 500 25 50

Utility Voltage V3

575 V AC +10% , -15%

Filter Current I3 (A)

20 40 70 140 210 280 420 20 40

Filter Current Neutral

3 x Line Current

Parallel Combination

Maximum 4 units of same power rating

Filter Power Loss

Upto 3% of equipment rating

Power Protection for Filter

2MCCB and Fast acting semiconductor fuses

Cooling

Forced Air cooling

Cable Entry

Front - Bottom

Current Transformer Ratio, CLASS 1 or better with 15 VA rating

19/01/1900 20:05:00 09/02/1900 16:05:00 04/05/1900 00:05:00 26/07/1900 08:05:00 06/09/1900 00:05:00 20/01/1900 20:05:00 10/02/1900 16:05:00

Harmonic Range

2nd to 50th order

Harmonics Selection

Selection of any 20 Harmonics

Harmonic Attenuation Ration

Upto 96% at rated current

Response Time

< 10 ms

Reactive Current Compensation

Yes

Priority Selection

Yes (PF and Harmonics)

Load Balancing

Yes

Filter Current Upgrading with Ambient Temperature

110% at 25°C, 105% at 30°C, 100% at 40°C, 80% at 50°C

User Interface

Monitoringe

IORAMON on Serial Port, IORAMON on Ethernet Port (Optional)

User Parameter Settings

From the system display or serially using software

Standard

Meets IEEE 519 for compensated Harmonics

Environmental

Protection Class

IP 20 (IP 31 optional)

Operating Temperature

0 to 40°C

Storage Temperature

0 to 70°C

Relative Humidity

95% (Non condensing)

Altitude

1000 m without derating

Color

RAL 7016, Texture Finish

Noise Level @ 1m (Ref ISO 3746)

< 65 dB < 68 dB < 65 dB

Dimensions in mm

Height

1000 1000 1750 1750 1750 1750 1750 1000 1000

Width

620 620 800 800 800 1000 1000 620 620

Depth

450 450 800 800 800 850 850 450 450