91+ 9823804196

svelectronics@live.com

PRODUCTS

FALCON 5000

Falcon 5000 range of IGBT based rectifier UPS systems are designed, for the data security and business continuity of today’s networked and cloud environment. Its unique modular design and compact footprint comes with variety of special features which are uncommon in this category of UPS Systems.

ADD TO WISHLITE

img-responsive
  • 32 bit DSP controlled UPS
  • IGBT based rectifier
  • Input current THDi 3%
  • Input PF near unity
  • Inbuilt galvanic isolation
  • Space vector modulation technique
  • 7.2" TFT Graphics Display
  • True RMS reading of more than 25 different parameters of UPS
  • High end interfacing options
  • Superior output quality ; Output voltage distortion 1%*
  • Unique modular design, offering lowest MTTR
  • Compact system, lowest footprint to kVA ratio in its category
  • Advance thermal design and monitoring

Rating in KVA

200 300 400 500 600

Input

Nominal Voltage

415 V AC 3 ph+N (± 15%)

Nominal frequency

50 Hz (46 to 54Hz) (60 Hz Optional)

Power Factor

≥ 0.99

THD i

< 3%

Topology

32 bit DSP controlled

Battery Voltage

600 V DC

Output

Power in KW

180 270 360 450 540

Power Factor

0.6 to Unity within KVA and KW rating

Voltage

400 V / 415 V AC (± 1%) 3 Ph (380V/ 440 V Optional)

Frequency

50 Hz (± 0.1 Hz)

Transient Response

± 5%, recovery within one cycle to 98%

Waveform

Sinusoidal

Total Harmonic Distortion

< 2% max for Linear Load, < 3% max for Non-Linear Load (Ref IEEE 62040-3)

Overload Capacity

110% for 60 min, 125% for 10 min, 150% for 60 sec

Inverter Efficiency (Ref. IEC 60146-1-1)

up to 96%, (ECO mode - up to 98 %)

Bypass

Voltage & Frequency

415 V AC , 15%, 50 Hz (± 2.5%)

Transfer Time

Synchronous mode : No break, Asynchronous mode < 10 ms

Environment

Operating Temperature

0 to 40° C

Storage Temperature

0 to 70° C

Relative Humidity

up to 95% RH (Non-condensing)

Maximum Operating Altitude

1000 m (without de-rating)

Acoustic Noise @ 1m (Ref. ISO 3746)

< 68 dBA < 70 dBA < 72 dBA < 74 dBA

Enclosure Protection Grade

IP 20

Ventilation

Forced air cooling

Cable Entry

Bottom

Dimensions in mm

Width

1400 1600 2100 2100

Depth

900 900 900 1000

Height

1750 1750 1750 1950

Cabinet Finish

RAL 7016, Texture Finish

Testing Standards/h2>

IEC 62040-3

Communication

Interface & Protocol

RS 232

Available Options

SNMP, MODBUS, Web based monitoring